150kVA Static Voltage Stabilizer Germany








ST-MAK Series 150kVA Static Voltage Stabilizer www.mak-powersis.de/150kva-static-voltage-stabilizer.html

INPUT Max 207kVA
Input Voltage 380 V AC Three Phase + Neutral (400 - 415 V AC Optional)
Input Voltage Tolerance 285V – 460V ( Phase – Notr) // -%25 / +%15 (Wide Range Optional)
Input Frequency 50 Hz. ( 60 Hz. Optional) + %5
Input Connection Suitable Terminal


OUTPUT  
Output Voltage 380 V AC Three Phase + Neutral (400 - 415 V AC Optional)
Output Voltage Tolerance + %2 ( + %1 Optional)
Outout Current 230A
Over Load % 101 - %125 Load 3 Min.
% 126 - %150 Load 10 Sec.
% 151 - Load Output Off in 0,2 Sec.
Output Frequency 50 Hz. ( 60 Hz. Optional) + %5
Regulation Speed 500 V/sec.
Efficiency > %97
Output Connection Suitable Terminal


GENERAL
LCD Display With 4x16 character LCD Display: Input Voltage, Output Voltage, % Output Load, Output Frequency, Regulator Condition and Failure Info, Over Load, Over Temperature, Input Failure warning ext.
Communication Through a software support and “Remote Management System"(RS-232 Communication port, Ethernet), the ability of monitoring and controlling


PROTECTION  
Output Voltage Protection When Output Voltage out of 340 V AC - 420 V AC tolerance values, Output Off with Contactor
Current Protection 1- Fuse protection with MCB at Input or Output
2 – Electronic Over Current Protection Via Microprocessors
By-Pass  Manuel By-Pass for Failure and Maintenance
Surge Arrester Suitable Surge Arrester unit for lightning and high voltage (Optional)
RFI Filter / Harmonic Filter RFI Filter / Harmonic Filter can be used to eliminate Input High frequency noises and Harmonic current (Optional)
Isolation Transformer Input and Output Isolation Transformer for special usage (Optional)
Operating Temperature -10 oC ~ +40 oC (-15 oC ~ +55 oC Optional)
Altitude < 3000 m
Humidity % 90 non condensed
Acoustic Noise < 50 dB
Dimension (WxDxH) 70cm x 140cm x 70cm
Weight 235 Kg


OPTIONS
Wide Input Voltage Range Please let us know needed input voltage range
Output Temperature -20 / +55 Celcious is Optional
Customized Solution Harmonic Filter / IP21 / IP22 / IP31 / IP41 / IP55 / IP65